IEC/TR 60725-2012 pdf free.Consideration of reference impedances and public supply network impedances for use in determining the disturbance characteristics of electrical equipment having a rated current s75 A per phase.
Three-phase, four-wire, distribution systems are used worldwide to supply low-voltage consumers with nominal voltages in the region of 230 V/400 V.
To conform with IEC standard voltages, these systems are described as 230 V/400 V throughout this report.
There is considerable variation in the way in which the supplies to individual consumers are connected to three-phase systems.
In some countries, all four wires are taken into the consumer’s premises, allowing the use of three-phase 400 V for large loads, with small appliances and lighting circuits connected between one line and neutral at 230 V.
In other countries, three wires are taken into the consumer’s premises, allowing the use of 400 V across two phases for large loads, with small appliances and lighting circuits connected between one line and neutral at 230 V.
In other countries, of which the United Kingdom is an example, it is unusual to take more than one phase into a residential consumer’s premises. Therefore, both large loads that are less than 15 kVA and lighting circuits are supplied between line and neutral at 230 V.
3.2 Single-phase two-wire supply systems
In the rural areas of most countries, it is common to connect the winding of distribution transformers across two phases of medium voltage systems and afford supplies to low- voltage consumers via a phase and return conductor. A wide range of voltage is associated with this type of supply system.
In Korea, there are extensive networks supplying single-phase two-wire connections at 220 V.
3.3 Single-phase three-wire supply systems
In some countries, of which the United States of America is an example, a single-phase, three-wire distribution is used. Large loads are connected across the outer wires at 240 V whilst small appliances and lighting circuits are connected between one outer and the centre wire at 120 V, as shown in Figure 1.IEC/TR 60725 pdf download.